Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 1:1 Inverter 185 H
Standard PAC SPW CR 184 GVH56B
PIPING
SUCTION
1/2"
1/4"
LIQUID
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
20 g/m
40m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
16a Single Phase
REMOTE CONTROLLER WIRING
WIRING DIAGRAM
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 1:1 Inverter 255 H
Standard PAC SPW CR 254 GVH56B / GVH8B
PIPING
SUCTION
5/8"
3/8"
LIQUID
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
40 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 20a Single Phase - GVH8B 10a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 1:1 Inverter 365 H
Standard PAC SPW CR 364 GVH56B / GVH8B
PIPING
SUCTION
5/8"
3/8"
LIQUID
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
40 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 25a Single Phase - GVH8B 10a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 1:1 Inverter 485 H
Standard PAC SPW CR 484 GVH56B / GVH8B
PIPING
SUCTION
5/8"
3/8"
LIQUID
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
40 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 32a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 1:1 Inverter 605 H
Standard PAC SPW CR 604 GVH56B / GVH8B
PIPING
SUCTION
5/8"
3/8"
LIQUID
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
40 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 40a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 2:1 Inverter 125 H
Standard PAC SPW CR 484 GVH56B / GVH8B
PIPING
SUCTION
5/8" to joint 1/2" from joint to indoor
LIQUID
3/8" to joint 1/4" from joint to indoor
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
3/8" = 40 g/m & 1/4" = 20 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 32a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 2:1 Inverter 255 H
Standard PAC SPW CR 484 GVH56B / GVH8B
PIPING
SUCTION
5/8"
3/8"
LIQUID
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
40 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 32a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 3:1 Inverter 165 H
Standard PAC SPW CR 484 GVH56B / GVH8B
PIPING
SUCTION
5/8" to joint 1/2" from joint to indoor
LIQUID
3/8" to joint 1/4" from joint to indoor
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
3/8" = 40 g/m & 1/4" = 20 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 32a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 3:1 Inverter 185 H
Standard PAC SPW CR 604 GVH56B / GVH8B
PIPING
SUCTION
5/8" to joint 1/2" from joint to indoor
LIQUID
3/8" to joint 1/4" from joint to indoor
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
3/8" = 40 g/m & 1/4" = 20 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 40a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 4:1 Inverter 125 H
Standard PAC SPW CR 484 GVH56B / GVH8B
PIPING
SUCTION
5/8" to joint 1/2" from joint to indoor
LIQUID
3/8" to joint 1/4" from joint to indoor
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
3/8" = 40 g/m & 1/4" = 20 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 32a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 4:1 Inverter 165 H
Standard PAC SPW CR 604 GVH56B / GVH8B
PIPING
SUCTION
5/8" to joint 1/2" from joint to indoor
LIQUID
3/8" to joint 1/4" from joint to indoor
GAS PRE CHARGE LENGTH
ADDITIONAL CHARGE
MAXIMUM PIPING LENGTH
30m
3/8" = 40 g/m & 1/4" = 20 g/m
50m
INTERCONNECTING WIRING
POWER SUPPLY WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
INDOOR UNIT POWER SUPPLY
OUTDOOR UNIT POWER SUPPLY
5a Single Phase
GVH56B 40a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
NUMBER OF CORES
0.75 mm (Shielded)
2
WIRING DIAGRAM
DOWNLOADS
|
Radio Shack Weather Radio 12 240 User Guide
RCA Network Router RC 930 User Guide
Revox Universal Remote Recontrol M207 User Guide
Ryobi Blower UT15519E User Guide
Samsung Air Conditioner WC12ZR User Guide
Samsung DVD Player AH68 01339B User Guide
Sanyo DVD Player DC TS750 User Guide
Seagate Computer Drive Ultra 160 User Guide
Sears Home Gym 831288261 User Guide
Sears Lawn Mower 91725958 User Guide